Hello there I am an Electrician out of Las Vegas I am doing a restaurant and I have not wire this a nsul system so I need some.help!! I leave my e mal
ayvrson_de_yi@yahoo.com.mx
Thanks
QUOTE=airservice co;805556]NO- Normaly open
NC- " closed
C- Common constant 110vac
MAKE SURE THE COMMON IN THE ANSUL BOX HAS A CONSTANT 110vac hot wire. (no need for neutral in the Ansul box.)
If you want something to go OFF(lights, outlets ect)
1st option NC to Contactor 110vac coil (use poles for diffrent circuts) Contactor stays closed... Ansul Activated, contactor opens ie. no power.
2nd option NO to a shunt breaker. ( a shunt breaker has 2 spaces behind the hot wires). Get a netural (white) anywhere. Wire the hot on the shunt breaker to NO...Ansul Activated , power to the shunt breaker, Trips breaker , No Power
To turn something on Wire a parrall contactor (110vac coil ) with the Fan switch and wire to NO. In effect bypassing the switch. 2 wires from the fan switch...wired top and bottom of your contactor is easy as pie.
SOMETIMES WHOLE PANEL BOXES ARE SHUNTED...The main is a shunt breaker. Wire that baby to the NO and the whole panel goes off. SWEET.
Make sure your ex. fan, or constant 110 to Ansul, is not in this panel![/QUOTE]