What KBR is doing in Afghanistan and Iraq has no bearing on this conversation. What is going on there is gross negligence and incompetence.
Who really knows what is happening there? Plumbing is being used for ground, but is mistakenly being heated up. Any Handyman99 can go to work for KBR an electrician, and when the hooking up the right colors becomes difficult, they only have to do what is easy, because no one can "prove" otherwise.
This thread has become a three pronged conversation:
(1) Is it a urban plumbing legend about someone getting shocked in the shower No, it isn't. I have personally seen it happen and found voltage at a shower faucet.
(2) Is a hot water heater thermostat SPST or DPDT? SPST
(3) Why isn't a GFCI required on a HWT? ( Answer, because it is redundant. It should be correctly grounded with a ground wire bundled with the conductors in conduit, NM, or MC, and ran all the way to the panel) Correct .