Fire Suppression System Micro Switch


I need help explaining to an electrician how to connect my micro switch to the elect. I've already installed the micro switch in my controll head. I can't not find a schmatic for him and just telling him Red is common, Yellow N.O. & Black N.C. and that all the elect under the hood needs to shut down except the exhaust fans stay on ... is not enough. Any suggestions?? All I have is a pic of the microswitch and not a schmatic.
firesafetylady is offline  

Warning: The topics covered on this site include activities in which there exists the potential for serious injury or death. ContractorTalk.com DOES NOT guarantee the accuracy or completeness of any information contained on this site. Always use proper safety precaution and reference reliable outside sources before attempting any construction or remodeling task!

   

Advertisement

 

Old 04-11-2011, 10:20 PM   #2
Capra aegagrus

 
Tinstaafl's Avatar
 
Trade: Remodeler
Join Date: Jan 2008
Location: Central Pennsylvania
Posts: 23,196
Rewards Points: 1,407

Re: Fire Suppression System Micro Switch


Quote:
Originally Posted by firesafetylady View Post
Any suggestions?? All I have is a pic of the microswitch and not a schmatic.
I would suggest that you find a real electrician, because that is an extremely elementary circuit that a 12 year old could understand.

Also, forgive my bluntness, but if you can't whip out a schematic for that on a paper napkin in about 5-10 seconds, maybe you shouldn't be fooling with the job in the first place.

Advertisement

Tinstaafl is offline  
Old 04-11-2011, 10:42 PM   #3
I own stock in FotoMat!
 
480sparky's Avatar
 
Trade: 132 on Bush, I've got him at gunpoint!
Join Date: Jan 2009
Location: Iowa
Posts: 11,944
Rewards Points: 11,756

Re: Fire Suppression System Micro Switch


Fire suppression systems many times need to do more than just shut down the MAU. They also must shut down any electrical under the hood (typically required with the new wet systems, no so much w/the old halon), and may even need to trigger the fire alarm system. Pretty tall order for a part with a wholesale cost of $1.37. There are some systems that have a sum total of two microswitches, but it still falls on the electrician to make the system function as required.

If the electrician on site is unable to figure out how to accomplish all this, perhaps the owner/GC should find someone qualified.
__________________
This post has been modified from its original version. It has been formatted to fit this screen and edited for content.
480sparky is online now  
The Following User Says Thank You to 480sparky For This Useful Post:
Tinstaafl (04-11-2011)
Sponsored Links
Advertisement
 
Old 04-12-2011, 01:06 AM   #4
Pro
 
fireguy's Avatar
 
Trade: Fire Suppression Equipment Sales & Service
Join Date: Oct 2006
Posts: 467
Rewards Points: 324

Re: Fire Suppression System Micro Switch


I do not understand how you could design and install a suppression system with out the install manual. Every install manual I have shows how to have the electrician wire the switches. If the electrician is not on site when I am ready for him, I print the schematic pages and leave them in the panel. I also print in BIG letters, "Make NO electrical connections in this mechanical panel. This panel is not listed for electrical connections. Make all connections outside this box".

What brand system is this?
fireguy is offline  
Old 04-12-2011, 02:26 AM   #5
Registered User
 
firesafetylady's Avatar
 
Trade: Fire Prevention & Safety
Join Date: Apr 2011
Posts: 4
Rewards Points: 10

Re: Fire Suppression System Micro Switch


Ansul ~ which shouldn't make any differance for the electrical hook up ...
firesafetylady is offline  
Old 04-12-2011, 02:33 AM   #6
Registered User
 
firesafetylady's Avatar
 
Trade: Fire Prevention & Safety
Join Date: Apr 2011
Posts: 4
Rewards Points: 10

Re: Fire Suppression System Micro Switch


I've already installed the micro switch in the panel with the wires feed outside the panel with instructions to make the connection outside the mechanical panel ~ which is my job ... what is not my area is hooking it up to the elect. I've checked 4 of the manuals that I have and not one system manufactures has instructions for the elect hook up only on installing the microswitch in there mech control head.

Last edited by firesafetylady; 04-12-2011 at 02:38 AM.
firesafetylady is offline  
Old 04-12-2011, 08:23 AM   #7
Head Grunt
 
woodchuck2's Avatar
 
Trade: Electrical Contractor&Home Maintenance
Join Date: Feb 2008
Location: North Creek, NY/Lower Adirondacks
Posts: 3,270
Rewards Points: 2,196

Re: Fire Suppression System Micro Switch


Still quite easy to figure out if this electrician is competent. At most he may have to use a meter and figure out which side of the switch is open or closed and then figure out if he is using shunt trip breakers or is he using relays?
woodchuck2 is offline  
Old 04-12-2011, 08:36 AM   #8
I own stock in FotoMat!
 
480sparky's Avatar
 
Trade: 132 on Bush, I've got him at gunpoint!
Join Date: Jan 2009
Location: Iowa
Posts: 11,944
Rewards Points: 11,756

Re: Fire Suppression System Micro Switch


Quote:
Originally Posted by firesafetylady View Post
I've already installed the micro switch in the panel with the wires feed outside the panel with instructions to make the connection outside the mechanical panel ~ which is my job ... what is not my area is hooking it up to the elect. I've checked 4 of the manuals that I have and not one system manufactures has instructions for the elect hook up only on installing the microswitch in there mech control head.
Then you've most likely completed your end of the contract. Any competent electrician should be able to figure out HIS part whether you're there or not.

Unless the system isn't 'standard', I rarely interact with the hood installers, even when we're concurrently on-site. And a single microswitch is about as standard as it gets.


Sounds like a very incompetent electrician has been hired by an almost equally incompetent builder.

Sparky: (Looking at microswitch wondering what the 3 wires are for, and how to connect his 2-wire circuit to it, thinking "this looks like a switch, and I know enough not to hook a hot and a neutral to a switch because that will cause a short. I'd better ask for some details before I proceed otherwise I'll look like an idiot) "Hey, Mr. Builder, I need you to call the Hood Guys for a wiring diagram on this!"...........

Builder: "OK, I'll call 'em!", (reaching for his phone, not knowing what to ask for or who to talk to and not having the gumption to ask Sparky otherwise he'll look like an idiot.....)
__________________
This post has been modified from its original version. It has been formatted to fit this screen and edited for content.
480sparky is online now  
Old 04-12-2011, 05:32 PM   #9
Registered User
 
firesafetylady's Avatar
 
Trade: Fire Prevention & Safety
Join Date: Apr 2011
Posts: 4
Rewards Points: 10

Re: Fire Suppression System Micro Switch


haha I love it ... thx and btw today didn't go well at all since there were other electrical issues with connects from the brakers. Another electrician is coming in the morning sooo, hopefully he can get it done lol Thank You!
firesafetylady is offline  
Old 06-08-2019, 11:34 AM   #10
Registered User
 
A-1tekniguard's Avatar
 
Trade: Electrical
Join Date: Jun 2019
Posts: 1
Rewards Points: 2

Re: Fire Suppression System Micro Switch


The electrician will wire the controls for this system. When the ansel system is activated there are normally 2 micro switches that switch. They have N.O. and N.C. contacts on each one. The normally closed contact will be used to activate the breaker that feeds the sub panel that will shut down and kill the power under the hood. Wire 120 volts to the com terminal on a switch and from the N.O. contact wire to the shunt trip breaker. The other side of the breaker goes to the neutral buss in the panel. This will energize the shunt trip in the breaker when the ansel system is set off which will shut down everything under the hood. This will all be wired from the sub panel fed by this breaker. Make sure the exhaust is powered from the main panel so it does not shut down at this time. This must run to get rid of the smoke. Only the make up air shuts down from the sub panel along with anything else electrical under the hood. Does this make sense to you now? Let me know A-1tekniguard Tallahassee......kaboom we are here to show and teach others not show off on others.
A-1tekniguard is offline  
Old 06-08-2019, 07:16 PM   #11
Pro
 
rrk's Avatar
 
Trade: remodeling
Join Date: Apr 2012
Location: new jersey
Posts: 5,624
Rewards Points: 1,696

Re: Fire Suppression System Micro Switch


This thread is 8 years old
rrk is online now  
The Following User Says Thank You to rrk For This Useful Post:
Dirtywhiteboy (06-08-2019)
Old 06-09-2019, 02:28 AM   #12
Pro
 
VinylHanger's Avatar
 
Trade: I'll do that for 500 bucks.
Join Date: Jul 2011
Location: Oregon
Posts: 9,734
Rewards Points: 10,456

Re: Fire Suppression System Micro Switch


Yeah, but a kaboom is timeless.

Sent from my SM-N950U using Tapatalk

Advertisement

__________________
Your emergency does not constitute a problem with my Constitution.
VinylHanger is online now  

Tags
electrical , fire suppresion system


Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes Rate This Thread
Rate This Thread:

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are Off
Refbacks are Off


Similar Threads
Thread Thread Starter Forum Replies Last Post
Ansul system wiring rad04 Electrical 16 07-27-2017 10:18 PM
New Fire Protection Guy banderson New Member Introductions 7 11-15-2010 06:23 AM
Fire Alarm system needed in Hatfeild, PA pinakin Help Wanted or Looking For Work 0 08-02-2010 07:44 AM
fire system rbring New Member Introductions 1 06-11-2010 12:47 AM
light and fan switch red_cedar Electrical 17 02-24-2010 07:54 AM

Join Now... It's Fast and FREE!

I am a professional contractor
I am a DIY Homeowner
Drywall Talk is for
PROFESSIONAL CONTRACTORS ONLY!

At DrywallTalk.com we cater exlusivly to professional contractors who make their living as a contractor. Knowing that many homeowners and DIYers are looking for a community to call home, we've created www.DIYChatroom.com DIY Chatroom is full of helpful advices and perfect for DIY homeowners.

Redirecing in 10 seconds
No Thanks
terms of service

Already Have an Account?