Second Floor Water Heater Drip Pan And T&P Drains

 
Thread Tools Search this Thread Display Modes
Old 07-18-2009, 10:30 AM   #1
Pro
 
bob_cntrctr's Avatar
 
Trade: renovator
Join Date: Jan 2008
Posts: 511

Second Floor Water Heater Drip Pan And T&P Drains


Gentlemen,

I think I posted a thread about this a couple of years ago, but, frankly, I've never been completely satisfied with this subject, so here goes again.

You've got a two storey home with full basement. Second storey bathrooms and an electric water heater in a service closet on the second floor.

The heater must sit in a drip pan and the drip pan must have a 3/4" drain. The T&P valve must also have a 3/4" drain and cannot terminate in the drip pan. Both must separately go either outside or drain into another drain, like a floor drain or a fixture.

In places where it's -10F two months of the year, noone wants to terminate outside. The second floor bathrooms don't have floor drains.

This is why I personally have yet to see a second floor water heater installed with every aspect of code satisfied. Maybe I just hang out in the wrong places.

So I'm working on a place, we've got the first floor ceilings and second floor walls open, it's really the right time to bring this up to code - - but frankly it looks like the "right" way to do it is to run two 3/4" drain lines all the way down to the basement to the floor drain or the sump. Which, if you ask me, completely defeates the purpose of the drain lines being visible so people can detect T&P problems, 'cause noone's gonna be checking out this dark corner of the basement regularly to see if there's a drip from these lines.

Maybe I'm just missing somthing.

Thanks.

bob_cntrctr is offline  
Warning: The topics covered on this site include activities in which there exists the potential for serious injury or death. ContractorTalk.com DOES NOT guarantee the accuracy or completeness of any information contained on this site. Always use proper safety precaution and reference reliable outside sources before attempting any construction or remodeling task!

Old 07-18-2009, 12:24 PM   #2
Thom
 
thom's Avatar
 
Trade: General Contractor/Homebuilder
Join Date: Nov 2006
Location: Albuquerque NM
Posts: 3,197

Re: Second Floor Water Heater Drip Pan And T&P Drains


I've done them where we set the water heater on a standard shower pan that is plumbed into the waste/vent system. The T&P terminates above the flood level rim of the shower pan as does the necessary trap primer.

It's simple, cheap, and the inspectors have looked favorably on the installation.
thom is offline  
Old 07-18-2009, 12:28 PM   #3
Pro
 
genecarp's Avatar
 
Trade: LI,NY designer, new homes, renovation work, concre
Join Date: Mar 2008
Location: Long Island, NY
Posts: 5,426

Re: Second Floor Water Heater Drip Pan And T&P Drains


Agreed with above post--------------vent
__________________
genecarp is offline  
Old 07-18-2009, 01:17 PM   #4
Pro
 
bob_cntrctr's Avatar
 
Trade: renovator
Join Date: Jan 2008
Posts: 511

Re: Second Floor Water Heater Drip Pan And T&P Drains


Ya, I was thinking just turn the closet into a mini-shower. Mine's not a standard shower pan size, but what the heck - so I'll mud a 20" shower. Doesn't have to be pretty.

By definition I've got the cold water line in there - perfect spot for a pressure-drop primer, it'll get acutated everytime anyone turns anything on in any bathroom.

Last edited by bob_cntrctr; 07-18-2009 at 01:32 PM.
bob_cntrctr is offline  
Old 07-18-2009, 01:47 PM   #5
Professional Instigator
 
rbsremodeling's Avatar
 
Trade: Design Build Remodeling Contractor DC MD
Join Date: Nov 2007
Location: Washington, DC/ Maryland
Posts: 6,872

Re: Second Floor Water Heater Drip Pan And T&P Drains


I do it like Tom suggested or use a condensate pump.
__________________

rbsremodeling is offline  
Old 07-18-2009, 07:52 PM   #6
Pro
 
bob_cntrctr's Avatar
 
Trade: renovator
Join Date: Jan 2008
Posts: 511

Re: Second Floor Water Heater Drip Pan And T&P Drains


Ho ho - shower pan - non-standard size - - 20" x 20" - - aha! A laundry tub! Cut down to a few inches tall - drain built in ready to go, no mudding - love it.
bob_cntrctr is offline  
Old 08-01-2009, 05:59 PM   #7
Pro
 
bob_cntrctr's Avatar
 
Trade: renovator
Join Date: Jan 2008
Posts: 511

Re: Second Floor Water Heater Drip Pan And T&P Drains


Just to update and close off this thread - I ended up mudding a traditional shower pan in the service closet and connecting a full drain with vent, then adding a trap primer on the toilet supply line. A 9" curb across the front of the closet and 6" of tile up the wall and curb. Nice little set up - everything can just drain into the floor of the service closet 'cause it's a shower.
bob_cntrctr is offline  
The Following User Says Thank You to bob_cntrctr For This Useful Post:
MACPLUMB (08-02-2009)
Old 08-01-2009, 10:58 PM   #8
the pipe master
 
protechplumbing's Avatar
 
Trade: plumbing, solar
Join Date: Oct 2008
Location: Central, Fl
Posts: 497

Re: Second Floor Water Heater Drip Pan And T&P Drains


Why can't you simply oversize and insulate the drains on the outside?

Quote:
Originally Posted by bob_cntrctr View Post
Gentlemen,

I think I posted a thread about this a couple of years ago, but, frankly, I've never been completely satisfied with this subject, so here goes again.

You've got a two storey home with full basement. Second storey bathrooms and an electric water heater in a service closet on the second floor.

The heater must sit in a drip pan and the drip pan must have a 3/4" drain. The T&P valve must also have a 3/4" drain and cannot terminate in the drip pan. Both must separately go either outside or drain into another drain, like a floor drain or a fixture.

In places where it's -10F two months of the year, noone wants to terminate outside. The second floor bathrooms don't have floor drains.

This is why I personally have yet to see a second floor water heater installed with every aspect of code satisfied. Maybe I just hang out in the wrong places.

So I'm working on a place, we've got the first floor ceilings and second floor walls open, it's really the right time to bring this up to code - - but frankly it looks like the "right" way to do it is to run two 3/4" drain lines all the way down to the basement to the floor drain or the sump. Which, if you ask me, completely defeates the purpose of the drain lines being visible so people can detect T&P problems, 'cause noone's gonna be checking out this dark corner of the basement regularly to see if there's a drip from these lines.

Maybe I'm just missing somthing.

Thanks.
__________________
Plumber, Repiping, Replumbing, Leak Detection, Solar Water Heater, Polk County Plumber, Lakeland Plumber, Winter Haven Plumber
protechplumbing is offline  


Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes Rate This Thread
Rate This Thread:

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are Off
Refbacks are Off


Similar Threads
Thread Thread Starter Forum Replies Last Post
T&p rex Plumbing 5 09-17-2007 01:35 AM

Join Now... It's Fast and FREE!

Privacy Badge
I am a professional contractor
I am a DIY Homeowner
ContractorTalk.com is for
PROFESSIONAL CONTRACTORS ONLY!

At ContractorTalk.com we cater exlusivly to professional contractors who make their living as a contractor. Knowing that many homeowners and DIYers are looking for a community to call home, we've created www.DIYChatroom.com DIY Chatroom is full of helpful advices and perfect for DIY homeowners.

Redirecing in 10 seconds
No Thanks
terms of service

Already Have an Account?