#1 |
|
Pro
Trade: Electrical & Carpentry
Join Date: Dec 2008
Location: Adirondacks of NY
Posts: 781
|
Pex Busted Before Copper-frozen
Got a call for our church hall yesterday with flooding on the main floor from a broken pipe. I found it out in the hallway entrance. It was the hot water baseboard Took the covers off & found that 3/4 pex tubing blown out from freezing on the return line which copper was piped on top of the finned radiator & then exited & adapted to pex & that was where it was blown out from freezing. Why didn't the copper supply line at the bottom freeze & bust first?? I thought the pex would allow more expansion.This Kind of Baffled me. The pex was more of a white color. Is it the right stuff? I had them call the guy that installed it to come and fix it.
I later found the reason for the freeze-up- an 1/8 " to 1/4" gap on the bottom of a new door someone installed. |
|
|
|
|
|
#2 |
|
President
Trade: Installing windows, siding, roofing, doors, patio rooms, gutters and shutters.
Join Date: Dec 2007
Location: Central Maine
Posts: 292
|
Re: Pex Busted Before Copper-frozen
I'm sure they got the door for a great price.
|
|
|
|
|
|
#3 |
|
Pro Plumber
Trade: Plumber
Join Date: Oct 2006
Posts: 2,779
|
Re: Pex Busted Before Copper-frozen
Post a picture of the pex that burst.
|
|
|
|
|
|
#4 |
|
Pro
Trade: Electrical & Carpentry
Join Date: Dec 2008
Location: Adirondacks of NY
Posts: 781
|
Re: Pex Busted Before Copper-frozen
Ron, I didn't get a picture of it before the guy fixed it, but I think he left it on the window sill there so I will look for it when I go down there to check on the place. It looked the same as a copper pipe would when it freezes & busts. Blown out with a big split horizontal on the pipe about 2" long.............Mike
P.S. I am not against pex, as I use it myself, but not in all situations so this one has got me with my thinking cap on & would like some other insight on it ! |
|
|
|
|
|
#5 |
|
Pro Plumber
Trade: Plumber
Join Date: Oct 2006
Posts: 2,779
|
Re: Pex Busted Before Copper-frozen
Yea please post a picture if at all possible. Too this date I have not encountered pex pipe burst, Pex pipe should be seamless so a seam split can be ruled out.
|
|
|
|
|
|
#6 |
|
Plumbing is a Profession
Trade: Plumbing & HVAC
Join Date: Sep 2008
Location: S. Maine
Posts: 157
|
Re: Pex Busted Before Copper-frozen
Ron, I have a piece of 3\4" heat pex with about an 1 1/2" smile in it. Also have a piece of 1/2" Viega with a nice little smile in it also. The 1/2" was inside a mobile home feeding the shower hot. The home had been without power for about two weeks. The 3/4 was run next to a large gap in the sill. At my apprentice class this evening we were discussing this very subject and several of my students have run across broken pex in the last couple of weeks.
|
|
|
|
|
|
#7 |
|
The Grand Wazoo
Trade: It blowed up real good!
Join Date: May 2007
Location: Illinois
Posts: 3,090
|
Re: Pex Busted Before Copper-frozen
I thought PEX was the wonder pipe that was light years better than copper?
__________________
A flush is better than a full house. |
|
|
|
|
|
#8 |
|
New Guy
Trade: residential/commercial plumbing contractor
Join Date: Jan 2009
Location: central ky
Posts: 25
|
Re: Pex Busted Before Copper-frozen
I do see pex get very hard/brittle acting in extreme cold, its the wersbo/heat type.
|
|
|
|
![]() |
| Thread Tools | Search this Thread |
| Display Modes | Rate This Thread |
|
|
Similar Threads
|
||||
| Thread | Thread Starter | Forum | Replies | Last Post |
| Pex vs Copper: Meter to house | stillwater | Plumbing | 51 | 09-17-2008 10:47 PM |
| Copper roofing | Trimac | Roofing | 2 | 08-21-2008 10:42 PM |
| Copper stripped from NJ cell phone towers | Celtic | Electrical | 12 | 01-25-2008 08:32 PM |
| Painting new gal. gutters copper | DeanV | Painting & Finish Work | 0 | 06-22-2006 09:39 PM |
| Copper vents -vs- plastic/aluminum | shopman | Roofing | 2 | 03-01-2006 08:51 AM |
| Go to Page... |