Xenon Pucks And Wall Cabinet Space?
I'd like to put xenon pucks into new glass front kitchen wall cabinets.
The cabinets will be 5 inches from the ceiling and have a trim and crown moulding on the top extending from the wall cabinet to the ceiling. Since I am renovating my kitchen, the drywall has been removed and I have the ability to run romex cable anywhere. How is this usually wired if there isn't an open space on top of the cabinets? My question: Is it ok to place the transformer on top of the cabinets in the 5" of space I have - behind the crown moulding? If this is ok, I assume it should be hardwired and not plugged into a new recepticle in this small space right? However, all the pucks I can find have the transformers plugged in. Thanks Last edited by LI Hardwood Guy; 02-17-2005 at 05:10 PM. |
|
|
|
|
|
#2 |
|
Electrical Contractor
Trade: Electrical
Join Date: Sep 2003
Location: NY State
Posts: 2,179
|
Re: Xenon Pucks And Wall Cabinet Space?
The most "legal" way to do this is to run CL2 low-voltage wire (ok for in wall use) to each light. Run this up into the attic and splice them all to the transformer secondary wire. Install a switched receptacle in an accessible spot and plug the transformer in.
__________________
|
|
|
|
|
|
#3 | |
|
New Guy
Join Date: Dec 2004
Posts: 23
|
Re: Xenon Pucks And Wall Cabinet Space?Quote:
What guage wire CL2 should I use for 18W pucks? And would a long length of this wire affect the current/lights? |
|
|
|
|
|
|
#4 |
|
Electrical Contractor
Trade: Electrical
Join Date: Sep 2003
Location: NY State
Posts: 2,179
|
Re: Xenon Pucks And Wall Cabinet Space?
If you "daisy chain" them go with 14 or 16 gauge. If the length is long (+50'), go at least 14.
__________________
|
|
|
|
![]() |