Water In Smoke Detector

 
Thread Tools Search this Thread Display Modes
Old 12-20-2008, 01:10 PM   #1
Registered User
 
Mozart Maestro's Avatar
 
Trade: General Contractor/Residential Renovations and Additions
Join Date: Jun 2008
Location: Chicago
Posts: 3
Question

Water In Smoke Detector


A customer called us about a smoke alarm going off in a home in Chicago that they purchased from us earlier this year. When they took the detector down, about 1/4 cup of water came out of the detector. The detector is on a vaulted ceiling in the second floor master bedroom.

The conduit serving this detector runs through unconditioned attic space. My hunch is that warm air is entering the box and condensing inside the conduit and flowing back down the pipe and dripping onto the detector.

One thought that is bugging me is why this is not occurring with the second smoke detector. The second unit has a vertical stub up into the attic and it connects the first unit. The second unit is outside a hall bathroom.

The R-38 insulation above the detector is dry; so I do not think there is a roof leak. The exhausts for the bathrooms and laundry are vented outside. There is an insulated HVAC duct close to the box for the detector.

I can't think of other possible moisture sources. My thought is to insulate the conduit to reduce the risk of condensation.


Last edited by Mozart Maestro; 12-20-2008 at 01:13 PM. Reason: clarification
Mozart Maestro is offline  
Warning: The topics covered on this site include activities in which there exists the potential for serious injury or death. ContractorTalk.com DOES NOT guarantee the accuracy or completeness of any information contained on this site. Always use proper safety precaution and reference reliable outside sources before attempting any construction or remodeling task!

Old 12-20-2008, 05:57 PM   #2
Pro
 
acrwc10's Avatar
 
Trade: Electrical contractor/General contractor/ ICC certified electrical inspector
Join Date: Dec 2006
Posts: 211

Re: Water In Smoke Detector


Or the water could have been in the pipe for a long time and just showed up as a problem now. for the AC line to be creating that much condensation inside of the EMT you would have other water issues showing up elsewhere in the attic.
acrwc10 is offline  
Old 12-20-2008, 06:03 PM   #3
Member
 
walkerj's Avatar
 
Trade: Electrical
Join Date: May 2007
Location: Louisiana
Posts: 43

Re: Water In Smoke Detector


Should have used romex
walkerj is offline  
Old 12-21-2008, 11:03 AM   #4
Baltimore Electrician
 
JohnJ0906's Avatar
 
Trade: Electrician
Join Date: Jan 2007
Location: Baltimore, MD
Posts: 1,249

Re: Water In Smoke Detector


Quote:
Originally Posted by Mozart Maestro View Post

The conduit serving this detector runs through unconditioned attic space. My hunch is that warm air is entering the box and condensing inside the conduit and flowing back down the pipe and dripping onto the detector.
300.7(A) You didn't/don't install seals?
__________________
John from Baltimore
"One Day at a Time"
All replies based on the 2008 NEC
Quote:
Originally Posted by celtic
Deny Everything, Admit Nothing, Demand Proof
JohnJ0906 is offline  
Old 12-21-2008, 09:28 PM   #5
Registered User
 
Mozart Maestro's Avatar
 
Trade: General Contractor/Residential Renovations and Additions
Join Date: Jun 2008
Location: Chicago
Posts: 3

Re: Water In Smoke Detector


Quote:
Originally Posted by JohnJ0906 View Post
300.7(A) You didn't/don't install seals?
Thanks for the insight.

The customer sent me an e-mail that more water came from the box since Friday.
Mozart Maestro is offline  


Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes Rate This Thread
Rate This Thread:

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are Off
Refbacks are Off


Similar Threads
Thread Thread Starter Forum Replies Last Post
Water Heater noises & air sputtering at faucets LarryS Plumbing 10 01-10-2009 10:41 PM
instant hot water mowpar Plumbing 6 03-23-2008 10:56 PM
smoke detector info for residential applications az electrician Electrical 6 04-06-2007 07:14 PM
Smoke Detector life expectancy Pearce Services Electrical 7 03-12-2007 09:36 PM
Smoke Detector Scam ABLE1 Electrical 4 03-07-2007 01:17 AM

Join Now... It's Fast and FREE!

Privacy Badge
I am a professional contractor
I am a DIY Homeowner
ContractorTalk.com is for
PROFESSIONAL CONTRACTORS ONLY!

At ContractorTalk.com we cater exlusivly to professional contractors who make their living as a contractor. Knowing that many homeowners and DIYers are looking for a community to call home, we've created www.DIYChatroom.com DIY Chatroom is full of helpful advices and perfect for DIY homeowners.

Redirecing in 10 seconds
No Thanks
terms of service

Already Have an Account?