Water In Smoke Detector
A customer called us about a smoke alarm going off in a home in Chicago that they purchased from us earlier this year. When they took the detector down, about 1/4 cup of water came out of the detector. The detector is on a vaulted ceiling in the second floor master bedroom.
The conduit serving this detector runs through unconditioned attic space. My hunch is that warm air is entering the box and condensing inside the conduit and flowing back down the pipe and dripping onto the detector. One thought that is bugging me is why this is not occurring with the second smoke detector. The second unit has a vertical stub up into the attic and it connects the first unit. The second unit is outside a hall bathroom. The R-38 insulation above the detector is dry; so I do not think there is a roof leak. The exhausts for the bathrooms and laundry are vented outside. There is an insulated HVAC duct close to the box for the detector. I can't think of other possible moisture sources. My thought is to insulate the conduit to reduce the risk of condensation. Last edited by Mozart Maestro; 12-20-2008 at 01:13 PM. Reason: clarification |
|
|
|
|
|
#2 |
|
Pro
Trade: Electrical contractor/General contractor/ ICC certified electrical inspector
Join Date: Dec 2006
Posts: 211
|
Re: Water In Smoke Detector
Or the water could have been in the pipe for a long time and just showed up as a problem now. for the AC line to be creating that much condensation inside of the EMT you would have other water issues showing up elsewhere in the attic.
|
|
|
|
|
|
#3 |
|
Member
Trade: Electrical
Join Date: May 2007
Location: Louisiana
Posts: 43
|
Re: Water In Smoke Detector
Should have used romex
|
|
|
|
|
|
#4 | |
|
Baltimore Electrician
Trade: Electrician
Join Date: Jan 2007
Location: Baltimore, MD
Posts: 1,249
|
Re: Water In Smoke Detector
300.7(A) You didn't/don't install seals?
__________________
John from Baltimore "One Day at a Time" All replies based on the 2008 NEC Quote:
|
|
|
|
|
|
|
#5 |
|
Registered User
Trade: General Contractor/Residential Renovations and Additions
Join Date: Jun 2008
Location: Chicago
Posts: 3
|
Re: Water In Smoke Detector |
|
|
|
![]() |
| Thread Tools | Search this Thread |
| Display Modes | Rate This Thread |
|
|
Similar Threads
|
||||
| Thread | Thread Starter | Forum | Replies | Last Post |
| Water Heater noises & air sputtering at faucets | LarryS | Plumbing | 10 | 01-10-2009 10:41 PM |
| instant hot water | mowpar | Plumbing | 6 | 03-23-2008 10:56 PM |
| smoke detector info for residential applications | az electrician | Electrical | 6 | 04-06-2007 07:14 PM |
| Smoke Detector life expectancy | Pearce Services | Electrical | 7 | 03-12-2007 09:36 PM |
| Smoke Detector Scam | ABLE1 | Electrical | 4 | 03-07-2007 01:17 AM |
| Go to Page... |