Three Hole Receps On A Ungrounded System?
Please advise.
I own a home that I am wanting to sell. It has a ungrounded, two wire, no ground wire, electrical system and newer three hole receps. To meet code, do I have to switch receps to the two hole receps or can I place the 'ungrounded' stickers on the three hole receps. Upgrading my electrical system is not an option. Thanks. Steve Unkie. |
|
|
|
|
|
#2 | |
|
DGFVT
Trade: Electrical
Join Date: Dec 2005
Posts: 885
|
Re: Three Hole Receps On A Ungrounded System?Quote:
Also the NEC section 406.3(D)(3)(b) states that GFCI’s are a legal substitute for a grounded outlet In an existing installation where there is no ground available in the outlet box. These just need to be labeled “No Equipment Ground”. These are couple of options and some body will come along and be able to quote you the whole NEC section 406.3(D)(3) if you do not have it and want to read the whole section about ungrounded receptacles. |
|
|
|
|
|
|
#3 |
|
Pro
Trade: REMODELING CONTRACTOR
Join Date: Jan 2006
Location: Port Orchard,WA
Posts: 139
|
Re: Three Hole Receps On A Ungrounded System?
Thank you very much.
Steve Unkie. |
|
|
|
![]() |
| Thread Tools | Search this Thread |
| Display Modes | Rate This Thread |
|
|
Similar Threads
|
||||
| Thread | Thread Starter | Forum | Replies | Last Post |
| Living Filter Septic System | jmic | Excavation & Site Work | 18 | 07-20-2007 09:31 PM |
| Back panel hole | england030 | Carpentry | 2 | 05-18-2007 10:05 PM |
| Systems Development List | Gordo | Business | 19 | 01-08-2007 07:28 PM |
| forced hot-water system | daniem1 | HVAC | 1 | 03-02-2006 05:37 AM |
| Hydronic hot air system, help??? | GMAN_2006 | HVAC | 1 | 02-27-2006 05:17 PM |
| Go to Page... |