#1 |
|
Registered User
Trade: electrical
Join Date: May 2005
Location: california
Posts: 14
|
Round House
im not to sure if that is the correct term but how many round house's(blk,red,blue,white,green thhn) can i put into a 3/4 conduit by code im not to sure of how many current caring conductors can be in the same conduit
|
|
|
|
|
|
#2 |
|
Pro
Trade: Master Electrican, Electrical Contractor
Join Date: Sep 2005
Posts: 348
|
Re: Round House
Hey doof, what size wire are you talking about?
|
|
|
|
|
|
#3 |
|
Electrical Contractor
Trade: Electrical Contractor
Join Date: Mar 2004
Location: Newnan GA
Posts: 744
|
Re: Round House
The amount of current carrying conductors can fill the pipe to a cross section of 40%. Of course after derating they may only be good for 10 amps. What size wire are you talking about?
BTW What is a round house???
__________________
We are the people (our parents warned us about) (Jimmy Buffett) Last edited by jbfan; 03-11-2006 at 07:04 AM. |
|
|
|
|
|
#4 |
|
Electrical Contractor
Trade: Electrical
Join Date: Sep 2003
Location: NY State
Posts: 2,179
|
Re: Round House
Mr. Doof,
Your profile says you are an electrician. Are you seriously asking this question? Especially the way it is worded?
__________________
Last edited by Speedy Petey; 03-11-2006 at 12:38 PM. |
|
|
|
|
|
#5 |
|
Registered User
Trade: electrical
Join Date: May 2005
Location: california
Posts: 14
|
Re: Round House
im not an electrical contrator im a aprentice my boss quizes me randomly since we are starting my first commercial job i just want to make sure i just want to make sure a can answer his question correctly the wire size is # 12thhn
|
|
|
|
|
|
#6 |
|
DGR,IABD
Trade: Electrical; Commercial and Residential Service
Join Date: Mar 2005
Location: Central PA
Posts: 9,680
|
Re: Round House
"Round House" is a regional slang term. Some of us may be more famaliar with the more popular term "full boat". Either slang phrase means a full 5 wire pull, consisting of a black, red, blue, white, green.
Exactly house many "round houses" doesn't make any sense in the context of the question. You only need one ground, sized to the largest conductor in the pull. Actually, you don't even need that if you're using a metallic raceway system, but current good trade practices dictate that you pull one. You may have up to 16 #12 THHN conductors in a 3/4" pipe. Once you have that many, you'll need to derate the ampacity of the conductors. |
|
|
|
|
|
#7 |
|
Pro
Trade: Master Electrican, Electrical Contractor
Join Date: Sep 2005
Posts: 348
|
Re: Round House
Ok then Doof the apprentice, it depends on wire size and type of raceway. You said #12, so now look in a current code book at annex C (back end of the book) in the appropriate table for each type of raceway. Annex C is not a mandatory thing, it is an informative table worked out so you don't fill past 40% conduit fill which is mandatory as another poster said. And once you fill this here conduit up, you now will have to consider de-rating issues, which in a nut shell means there will be less amps allowed on your #12 wire depending on how many more than three conductors are in the conduit. I bet your boss doesn't have all the different types of conduit/fill allowances memorized, so now is your chance to turn the tables on him. You memorize maximum fill for #12 for several types, then try quizzing him on liquid tight, flex, schedule 80, and so forth. When you are an apprentice you should try reading the code book for about at least 1/2 hour per day every day. And keep asking questions. You won't be a doof very long this way.
|
|
|
|
|
|
#8 |
|
Registered User
Trade: electrical
Join Date: May 2005
Location: california
Posts: 14
|
Re: Round House
thanx for all your advice guys i appreciate it
by the way the do0 is my nick name and a f4i is the type of motorcycle i ride but i can settle for doof lol |
|
|
|
|
|
#9 | |
|
Pro
Trade: Builder, Additions, large remodels...Lately also small remodels.......
Join Date: Nov 2005
Location: Portland Oregon
Posts: 889
|
Re: Round HouseQuote:
|
|
|
|
|
|
|
#10 |
|
GC/JE
Trade: electrical
Join Date: Jan 2006
Location: Odessa, Tx
Posts: 32
|
Re: Round House
Also, if you can, take some night classes. They should count as work time for your journeymans' requirements. And read everything you can.
Peace out.
__________________
Steve "Keep thee thy airspeed, lest the earth rise up and smite thee!" |
|
|
|
|
|
#11 |
|
listen twice talk once!
Trade: electrician
Join Date: Oct 2005
Location: Orange county California
Posts: 668
|
Re: Round House
How about nine. current carrying conductors that is. So nine if your using #12 and still going to put them on 20 amp breakers. So that is only two full round houses. unless of course you have balanced loads and do not have to count the nuetral then it's three. ...............go wings!
|
|
|
|
|
|
#12 |
|
New Guy
Trade: general contractor
Join Date: Mar 2006
Posts: 15
|
Re: Round House
Mr. Doof, You would probably be best to pick up a copy of "UGLY'S" (check with your local bookstore or electrical supply house) and you can start to answer the bosses questions on your own. If you are going to be a good electrican than you need to become resourceful. It is much easier to pull out your book and find the answer (1-2 minutes), than to get confused by multiple answers. The last time I checked - the book was about $8 and it is small enough to fit in your back pocket or tool pouch - and it doesn't lie. Also, thhn is not a size of wire it is a type of insulation or jacket. You will also need to know what type of conduit you will be pulling through (rigid, imc, emt, pvc sch40, pvc sch80, sealtight, flex, etc.) because the maximum # of conductors may vary. By the way, aprentice is spelled apprentice and should be preceded with "an" instead of "a". Also, it is carrying not caring. Good Luck Dude - ak
Last edited by wildwood; 03-31-2006 at 10:15 PM. |
|
|
|
![]() |
| Thread Tools | Search this Thread |
| Display Modes | Rate This Thread |
|
|
Similar Threads
|
||||
| Thread | Thread Starter | Forum | Replies | Last Post |
| Did you see Flip this house - Cat House? | SuperiorBuilt | Off Topic (Non Trade) | 18 | 01-24-2011 05:17 PM |
| Question with quarter round | haskl33 | Carpentry | 14 | 05-31-2008 07:49 AM |
| House moving | Toolwh@#e | Excavation & Site Work | 10 | 10-21-2007 11:23 PM |
| `Flip This House' star accused of fraud | AmeliaP | General Discussion | 28 | 06-03-2007 10:21 PM |
| Funding for first spec house? | ruskent | Business | 28 | 01-17-2006 08:10 PM |
| Go to Page... |