Old 09-30-2009, 03:28 PM   #1
Registered User
 
artisanelect's Avatar
 
Trade: Electrician
Join Date: Aug 2008
Location: NJ
Posts: 5

Rough Inspection


Hello, I am doing a basment remodel, my question is does the inspectors want to see the recessed lights in place, (it will be a drop ceiling)

I know all the other items that have to be done just not sure about the lights, I was just going to drop a temp light where the first light would go.

Thanks.

artisanelect is offline  
Warning: The topics covered on this site include activities in which there exists the potential for serious injury or death. ContractorTalk.com DOES NOT guarantee the accuracy or completeness of any information contained on this site. Always use proper safety precaution and reference reliable outside sources before attempting any construction or remodeling task!

Old 09-30-2009, 03:42 PM   #2
And I do electrical, too!
 
480sparky's Avatar
 
Trade: DEFENDER OF FREEDOM! ADVOCATE OF LIBERTY!
Join Date: Jan 2009
Location: Iowa
Posts: 5,391

Re: Rough Inspection


I've never had an inspector require recessed cans in place for a rough if it's going to be a drop ceiling.
__________________
Site : the area or exact plot of ground on which anything is, has been, or is to be located.
Sight : The power or faculty of seeing; perception of objects by use of the eyes; vision.
Cite : To mention in support, proof, or confirmation; refer to as an example.
480sparky is offline  
Old 09-30-2009, 03:52 PM   #3
Registered User
 
artisanelect's Avatar
 
Trade: Electrician
Join Date: Aug 2008
Location: NJ
Posts: 5

Re: Rough Inspection


Thanks, thats what I was thinking, I just wanted to double check.
artisanelect is offline  
Old 09-30-2009, 05:40 PM   #4
Fentoozler
 
Celtic's Avatar
 
Trade: Professional Pie and Pastry Taster
Join Date: May 2007
Location: New Jersey
Posts: 5,585

Re: Rough Inspection


Quote:
Originally Posted by 480sparky View Post
I've never had an inspector require recessed cans in place for a rough if it's going to be a drop ceiling.
Around here they are usually installed somewhere between the "rough" and "final" inspection....but BEFORE the ceiling inspection
__________________


The UD is quite possibly man kinds finest accomplishment.
Celtic is offline  
Old 09-30-2009, 06:00 PM   #5
Service & Repairs
 
Magnettica's Avatar
 
Trade: Electrician
Join Date: Dec 2006
Location: Rahway, New Jersey
Posts: 3,998

Re: Rough Inspection


Tell the inspector of your plan (how many lights, etc), then offer to leave a tile or two open so he'll be able to see the work.
Magnettica is offline  
The Following User Says Thank You to Magnettica For This Useful Post:
ampman (09-30-2009)
Old 10-06-2009, 01:41 PM   #6
Pro
 
Ohmy's Avatar
 
Trade: Electrical Contractor
Join Date: Sep 2009
Location: Atlanta, Georgia
Posts: 132

Re: Rough Inspection


You can do it two ways. First, the commercial building way where you get a wall cover, ceiling cover, and final. We use this method for basements with drop ceilings. The second method is to install all the recessed lights (putting in the tiles you need for the lights yourself) and call of the rough. Either way, a good inspector will want a ladder set up and a ceiling tile removed on the final as well.
Ohmy is offline  
Old 10-11-2009, 04:32 AM   #7
huntington beach, ca.
 
hbelectric's Avatar
 
Trade: electrical
Join Date: Oct 2007
Posts: 362

Re: Rough Inspection


If the ceiling grid is in, then put the tile in and install the can. Obviously if there is no grid you , you could just hang the can. Can lights are rough, so better install it.
hbelectric is offline  


Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes Rate This Thread
Rate This Thread:

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are Off
Refbacks are Off


Similar Threads
Thread Thread Starter Forum Replies Last Post
Heat Exchanger Inspection Methods Symposium MechAcc HVAC 3 08-15-2009 02:10 PM
Ahh it's a good day today! But a rough week J-Peffer Roofing 4 09-01-2008 02:06 AM
rough in inspection chris n General Discussion 10 09-27-2007 06:10 PM
Residential Rough in Estimate Central Florida Surface Tension Plumbing 7 06-17-2007 12:23 AM

Join Now... It's Fast and FREE!

Privacy Badge
I am a professional contractor
I am a DIY Homeowner
ContractorTalk.com is for
PROFESSIONAL CONTRACTORS ONLY!

At ContractorTalk.com we cater exlusivly to professional contractors who make their living as a contractor. Knowing that many homeowners and DIYers are looking for a community to call home, we've created www.DIYChatroom.com DIY Chatroom is full of helpful advices and perfect for DIY homeowners.

Redirecing in 10 seconds
No Thanks
terms of service

Already Have an Account?