10-27-2009, 02:01 AM
|
#1
|
|
huntington beach, ca.
Trade:
electrical
Join Date: Oct 2007
Posts: 313
|
Replacing Low Voltage can light transformer
Short story, a retro-fitting company( ie friend of mine), not licensed. Installed the wrong type of Occupency sensors in a beautiful multi-million brand new building and burned up 32- 277 volt low voltage magnetic ballast can lights.
He hired me to go straighten this mess out, my question would be, can I install a LV electronic ballast in each can? Should it be a manufacture spec transformer? or just any 277v magnetic trans? Or who knows where I can buy a 277v/12v transformer?
|
|
|
Warning: The topics covered on this site include activities in which there exists the potential for serious injury
or death. ContractorTalk.com DOES NOT guarantee the accuracy or completeness of any information contained on this site. Always use proper safety precaution and reference reliable outside sources before attempting any construction or remodeling task!
Join the #1 Contractor Forum Today - It's Totally Free!
ContractorTalk.com - Are you a Professional Contractor? If so we invite you to join our community and see what it has to offer. Our site is specifically designed for you and it's the leading place for contractors to meet online. No homeowners asking DIY questions. Just fellow tradesmen who enjoy talking about their business, their trade, and anything else that comes up. No matter what your trade is you'll find that ContractorTalk.com is a great community to join. Best of all it's totally free!
Join ContractorTalk.com - Click Here

|
10-30-2009, 09:12 PM
|
#3
|
|
huntington beach, ca.
Trade:
electrical
Join Date: Oct 2007
Posts: 313
|
My question is should I replace the ballast, with a direct factory replacement? So far the OEM has not returned my calls or email.
They use a magnetic 277 volt ballast, but it has to fit inside the fabricated box in the can, so it can't be just any ballast.
I'm also asking if I can use a Electronic ballast, where is it defiantly smaller and easier to buy, but it is not original.
I'm concerned that I replace these ballast, with non factory replacement, I might have some type of liability issues, that I don't want. In fact, I will write in my contract, no warranty, no responsibility for jack.
|
|
|
10-30-2009, 09:35 PM
|
#4
|
|
God Bless America
Trade:
Electrician
Join Date: Dec 2006
Location: Rahway, New Jersey
Posts: 3,400
|
Just replace all the fixtures unless you want to be held liable for re-using blown up hi-hats that some other "electrician" damaged badly and you rewired.
|
|
|
10-31-2009, 03:45 PM
|
#5
|
|
huntington beach, ca.
Trade:
electrical
Join Date: Oct 2007
Posts: 313
|
Quote:
Originally Posted by Magnettica
Just replace all the fixtures unless you want to be held liable for re-using blown up hi-hats that some other "electrician" damaged badly and you rewired.
|
The fixtures are recessed 277v 4" IC rated can lights. New construction style, box style fixture, hard lid ceiling, no access above ceiling. Commercial office building.
I appreciate your reply, that is a pretty good idea, not possible and a remodel would not be code.
|
|
|
11-01-2009, 07:59 AM
|
#6
|
|
Baltimore Electrician
Trade:
Electrician
Join Date: Jan 2007
Location: Baltimore, MD
Posts: 1,197
|
Quote:
Originally Posted by hbelectric
The fixtures are recessed 277v 4" IC rated can lights. New construction style, box style fixture, hard lid ceiling, no access above ceiling. Commercial office building.
|
It will be fun changing those ballasts.
Actually, damn near impossible.
__________________
John from Baltimore
"One Day at a Time"
All replies based on the 2008 NEC
Quote:
|
Originally Posted by celtic
Deny Everything, Admit Nothing, Demand Proof
|
|
|
|
11-01-2009, 04:56 PM
|
#7
|
|
huntington beach, ca.
Trade:
electrical
Join Date: Oct 2007
Posts: 313
|
Quote:
Originally Posted by JohnJ0906
It will be fun changing those ballasts.
Actually, damn near impossible.
|
I removed a ballst out of one, it is actually a good design, to work with.
|
|
|
11-02-2009, 05:30 PM
|
#8
|
|
New Guy
Trade:
Electrical
Join Date: Sep 2009
Posts: 25
|
I'm sure your buddy would love you to do this as cheap as possible, but if you change those ballasts out with non-standard ones .. and they give problems.. is he that much of a buddy that he'll cover the costs for you to go back and replace them a second time?
If he is? ... send me his name and number, i can always use a buddy like that.
IMO .. a ballast is a ballast, shouldn't make too much of a difference.
However once you start putting non-standard pieces in fixtures your taking on the role of an engineer and CSA ( i'm Canadian ) takes a very dim view of that.
The second problem is that God forbid there is ever a fire .. the insurance companies would eat you alive if they found out that you had replaced the ballasts with one that wasn't approved for that use.
Last edited by Immanuel; 11-02-2009 at 05:41 PM.
|
|
|
11-03-2009, 01:10 AM
|
#9
|
|
huntington beach, ca.
Trade:
electrical
Join Date: Oct 2007
Posts: 313
|
Quote:
Originally Posted by Immanuel
I'm sure your buddy would love you to do this as cheap as possible, but if you change those ballasts out with non-standard ones .. and they give problems.. is he that much of a buddy that he'll cover the costs for you to go back and replace them a second time?
If he is? ... send me his name and number, i can always use a buddy like that.
IMO .. a ballast is a ballast, shouldn't make too much of a difference.
However once you start putting non-standard pieces in fixtures your taking on the role of an engineer and CSA ( i'm Canadian ) takes a very dim view of that.
The second problem is that God forbid there is ever a fire .. the insurance companies would eat you alive if they found out that you had replaced the ballasts with one that wasn't approved for that use.
|
Thank you. The manufacturing finally got back with me, so hopefully they will tell me where to buy them or send me some free ones.
|
|
|
11-07-2009, 07:16 AM
|
#10
|
|
Baltimore Electrician
Trade:
Electrician
Join Date: Jan 2007
Location: Baltimore, MD
Posts: 1,197
|
Quote:
Originally Posted by hbelectric
The fixtures are recessed 277v 4" IC rated can lights. New construction style, box style fixture, hard lid ceiling, no access above ceiling. Commercial office building.
.
|
Quote:
|
Originally Posted by JohnJ0906
It will be fun changing those ballasts.
Actually, damn near impossible.
|
Quote:
Originally Posted by hbelectric
I removed a ballst out of one, it is actually a good design, to work with.
|
You removed it through the 4" recessed opening?
__________________
John from Baltimore
"One Day at a Time"
All replies based on the 2008 NEC
Quote:
|
Originally Posted by celtic
Deny Everything, Admit Nothing, Demand Proof
|
|
|
|
11-08-2009, 11:11 PM
|
#11
|
|
huntington beach, ca.
Trade:
electrical
Join Date: Oct 2007
Posts: 313
|
http://www.prescolite.com/products/s...fr_inc_025.pdf
This is the fixture, very easy to remove. My buddy just found out he is not getting paid for this job, so I don't think I will be going back for the repair. Was quoted $30 per ballast =14 ballast x30= $420+tax+labor wow what a screw up.
|
|
|
11-15-2009, 02:36 AM
|
#12
|
|
Baltimore Electrician
Trade:
Electrician
Join Date: Jan 2007
Location: Baltimore, MD
Posts: 1,197
|
Quote:
Originally Posted by hbelectric
|
Looks a lot easier than the ones I have done.
Quote:
|
My buddy just found out he is not getting paid for this job, so I don't think I will be going back for the repair. Was quoted $30 per ballast =14 ballast x30= $420+tax+labor wow what a screw up.
|
He's not being paid for the job, or not being paid to fix the screw-up?
__________________
John from Baltimore
"One Day at a Time"
All replies based on the 2008 NEC
Quote:
|
Originally Posted by celtic
Deny Everything, Admit Nothing, Demand Proof
|
|
|
|
11-15-2009, 11:27 AM
|
#13
|
|
Electrosexual
Trade:
Electrical Contractor
Join Date: Oct 2009
Location: L O S A N G E L E S
Posts: 179
|
There's been a couple of times I've converted existing fluorescent cans to incandescent by opening the j-box from inside the can and changing things. It's totally do-able, so changing ballasts is no big deal. But not for free.
|
|
|