Penetration At 2-hour Separation


we're building a 5b rated building, nursery school under offices. the nursery school has a 2-hour separation top / bottom and on all load bearing members. my electrician is telling me that its BX inside the 2-hour rated area. Does anyone know if these are BX home runs to the main panel or are we allowed to terminate at sub-panels just outside the 2-hour rated envelope and go with Romex from these sub-panels to the main? We're IBC.

wheeler is offline  
Warning: The topics covered on this site include activities in which there exists the potential for serious injury or death. ContractorTalk.com DOES NOT guarantee the accuracy or completeness of any information contained on this site. Always use proper safety precaution and reference reliable outside sources before attempting any construction or remodeling task!

Old 02-08-2009, 07:05 PM   #2
Service & Repairs
 
Magnettica's Avatar
 
Trade: Electrician
Join Date: Dec 2006
Location: Rahway, New Jersey
Posts: 3,998

Re: Penetration At 2-hour Separation


BX to sub panels and romex back to the mains? What in God's green earth are you talking about?

Btw, what state is this in?
Magnettica is offline  
Old 02-08-2009, 07:17 PM   #3
Member
 
wheeler's Avatar
 
Trade: design / build defense contractor
Join Date: Feb 2009
Location: Hamden, CT
Posts: 90

Re: Penetration At 2-hour Separation


Quote:
Originally Posted by Magnettica View Post
BX to sub panels and romex back to the mains? What in God's green earth are you talking about?

Btw, what state is this in?
ct.

my electrician has me running bx inside the 2-hour envelope. i don't want to run it to the main if we don't have to, its a large building.
wheeler is offline  
Old 02-08-2009, 07:20 PM   #4
DGR,IABD
 
mdshunk's Avatar
 
Trade: Electrical; Commercial and Residential Service
Join Date: Mar 2005
Location: Central PA
Posts: 9,680

Re: Penetration At 2-hour Separation


Quote:
Originally Posted by wheeler View Post
ct.

my electrician has me running bx inside the 2-hour envelope. i don't want to run it to the main if we don't have to, its a large building.
What would you rather use? I know you can't run romex in that construction type, anyplace.
mdshunk is offline  
Old 02-08-2009, 07:45 PM   #5
Service & Repairs
 
Magnettica's Avatar
 
Trade: Electrician
Join Date: Dec 2006
Location: Rahway, New Jersey
Posts: 3,998

Re: Penetration At 2-hour Separation


I guess you're going to have install some conduit from the MDP to a sub panel and tie your armored cables in there.
Magnettica is offline  
Old 02-09-2009, 06:01 AM   #6
Member
 
wheeler's Avatar
 
Trade: design / build defense contractor
Join Date: Feb 2009
Location: Hamden, CT
Posts: 90

Re: Penetration At 2-hour Separation


Quote:
Originally Posted by Magnettica View Post
I guess you're going to have install some conduit from the MDP to a sub panel and tie your armored cables in there.
check, thanks.
wheeler is offline  


Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes Rate This Thread
Rate This Thread:

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are Off
Refbacks are Off


Similar Threads
Thread Thread Starter Forum Replies Last Post
High Speed Cable & P.O.T. Separation? redzthredz Low Voltage 11 12-01-2009 05:09 PM
Do you charge more per Hour if Homeowner is "helping"? guyute65045 Excavation & Site Work 13 10-21-2008 09:24 PM
One hour fire rating for a truss AlLockrem Drywall 2 09-18-2008 10:31 PM
Plywood w/one hour fire rating fireguy Commercial Construction 8 09-18-2008 06:44 PM
Question about man hour rates Dorman Painting Painting & Finish Work 9 05-03-2006 07:35 PM

Join Now... It's Fast and FREE!

Privacy Badge
I am a professional contractor
I am a DIY Homeowner
ContractorTalk.com is for
PROFESSIONAL CONTRACTORS ONLY!

At ContractorTalk.com we cater exlusivly to professional contractors who make their living as a contractor. Knowing that many homeowners and DIYers are looking for a community to call home, we've created www.DIYChatroom.com DIY Chatroom is full of helpful advices and perfect for DIY homeowners.

Redirecing in 10 seconds
No Thanks
terms of service

Already Have an Account?