3 Phase Calculation HELP


I am a residential electrician needing help with some 3 phase calculations. The questions on a test I am taking are as follows:
1) How many watts are available in a 60 amp, 208 volt, 3 phase service?
2) How many 20 amp, 120 volt, 1 phase services can you support froma 100 amp, 208 volt, 3 phase distribution panel?
3) What size conductor is required for a 100 amp, 208 volt, 3 phase service less than 100 feet in length? More than 300 ft in length?
4) What size and how many conductors are requires for a 400 amp, 480 volt, 5 wire parallel, 3 phase service?
5) What is the maximum amperage available in a 45 kva, step-down 480 volt to 208 volt transformer?
6) If you were asked to install a 72,000 watt, 208 volt, 3 phase service, how many amps would this be?

can not find the formula in the ugly's book
i don't have the power factor

southern elec is offline  
Warning: The topics covered on this site include activities in which there exists the potential for serious injury or death. ContractorTalk.com DOES NOT guarantee the accuracy or completeness of any information contained on this site. Always use proper safety precaution and reference reliable outside sources before attempting any construction or remodeling task!

Old 02-06-2007, 04:41 PM   #2
Electrical Contractor
 
Speedy Petey's Avatar
 
Trade: Electrical
Join Date: Sep 2003
Location: NY State
Posts: 2,179

Re: 3 Phase Calculation HELP


Quote:
Originally Posted by southern elec View Post
I am a residential electrician needing help with some 3 phase calculations. The questions on a test I am taking are as follows:
.
.
.
can not find the formula in the ugly's book
i don't have the power factor
Residential or not, calculations are calculations.

How about try a code book as opposed to the Ugly's book???



BTW - At least three of those questions are erroneous at best.
__________________

Speedy Petey is online now  
Old 05-19-2007, 02:30 PM   #3
Registered User
 
skeeter's Avatar
 
Trade: electrician
Join Date: May 2007
Location: Colorado
Posts: 8

Re: 3 Phase Calculation HELP


there are a few examples in the back of the code book, like sp said use the code book.
skeeter is offline  
Old 05-19-2007, 02:39 PM   #4
DGR,IABD
 
mdshunk's Avatar
 
Trade: Electrical; Commercial and Residential Service
Join Date: Mar 2005
Location: Central PA
Posts: 9,680

Re: 3 Phase Calculation HELP


Southern electrician? Are you really an electrician? Recently apprenticed?
mdshunk is offline  
Old 05-19-2007, 03:32 PM   #5
Member
 
jbwhite's Avatar
 
Trade: Electrician
Join Date: Jan 2007
Location: New Bern, NC
Posts: 60

Re: 3 Phase Calculation HELP


I do not see any power factor involved in any of those questions

I also do not see why the Ugly's book needs bashed. In fact all of the information needed to answer the above questions are in there.
jbwhite is offline  
Old 05-19-2007, 04:08 PM   #6
Pro
 
ABLE1's Avatar
 
Trade: Security Alarm Installer (Low Voltage)
Join Date: Apr 2005
Location: Pennsylvania
Posts: 749

Re: 3 Phase Calculation HELP


Excuse me Gentlemen!!!

The original post was from Feb. 07. Southern Elec. either failed the test and went on to other things or passed and is making lots of profit and too busy to come here.

BTW I like the Ugly Book really good.

Les
__________________
ABLE1
ABLE1 is offline  
Old 05-19-2007, 06:07 PM   #7
Service & Repairs
 
Magnettica's Avatar
 
Trade: Electrician
Join Date: Dec 2006
Location: Rahway, New Jersey
Posts: 3,998

Re: 3 Phase Calculation HELP


www.MikeHolt.com

!!!!

Hope this helps:

Magnettica is offline  
Old 05-19-2007, 08:41 PM   #8
Electrical Contractor
 
Speedy Petey's Avatar
 
Trade: Electrical
Join Date: Sep 2003
Location: NY State
Posts: 2,179

Re: 3 Phase Calculation HELP


I was not bashing the Ugly's book. It does have it's place.
I am just so used to using the code book and Handbook I do not care for the Ugly's. I can find stuff just as fast using a code book.

Also, the OP stated he could not find something in the Ugly's book. I suggested he try the real code book. Maybe he could find what he needed there.

No offense was meant to Ugly's fans.
__________________

Speedy Petey is online now  
Old 05-20-2007, 08:40 AM   #9
Baltimore Electrician
 
JohnJ0906's Avatar
 
Trade: Electrician
Join Date: Jan 2007
Location: Baltimore, MD
Posts: 1,249

Re: 3 Phase Calculation HELP


Granted, the NEC is, and should be, the "bible" of our trade. However, I use the uglies for looking up something quick, since it is small enough to tuck in my tool bag, and the NEC is in the truck. It all depends.
I think one of the points of education is to learn to use the codebook, so someone preparing for a test should be using the NEC.
__________________
John from Baltimore
"One Day at a Time"
All replies based on the 2008 NEC
Quote:
Originally Posted by celtic
Deny Everything, Admit Nothing, Demand Proof
JohnJ0906 is offline  
Old 05-20-2007, 09:33 AM   #10
DGR,IABD
 
mdshunk's Avatar
 
Trade: Electrical; Commercial and Residential Service
Join Date: Mar 2005
Location: Central PA
Posts: 9,680

Re: 3 Phase Calculation HELP


I carry an Ugly's, but I'm not exactly sure why. Crane hand signals is the last time I remember referencing it. That's not really in the NEC. I'll probably give it to the next guy that shows an interest in it. When I catch people gawking at something of mine that I hardly ever use, like tools I thought would be useful and they aren't, I just give it to them if they want it. It seems like a vendor will give me an Ugly's every 4 or 5 years anyhow, so I'm probably due for a new copy.
mdshunk is offline  
Old 06-13-2007, 11:24 AM   #11
Member
 
jbelectric777's Avatar
 
Trade: NJ Lic Electrical Contractor
Join Date: Jun 2007
Location: NJ~PA
Posts: 67

Re: 3 Phase Calculation HELP


In three phase calculations just remember the square root of the number 3 (1.732)..... and include it in all your calcs. Example for your questions 1 & 2:

1) 208V X 1.732(360.25) X 60A = 21,615 or round to 21.6KVA

2) 208V X 1.732(360.25) X 100A= 36,025 or round to 36KVA
36000VA / 2400VA (20A 120V) = 15 20A Branch circuits.

Keep in mind the above calcs are basic theory only and are not taking into account continuous loads or other NEC demand factors. Also in one of your questions you used the word " Services " where I think you meant " Branch circuits "

I always took the voltage (E) and multiplied it by 1.732, other people leave the (E) alone and increase the VA or KVA either way it works out. Good Luck on your exam..... The above is how I learned it and used on all my exams.
__________________
" For all those whom beleive in Telekinesis, Raise my Right Arm"
jbelectric777 is offline  


Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes Rate This Thread
Rate This Thread:

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are Off
Refbacks are Off


Similar Threads
Thread Thread Starter Forum Replies Last Post
Single to 3 phase invertors/converters?? bantanic Electrical 17 02-14-2007 09:41 PM
3 phase 600 amp 240/120 panel bhe Electrical 10 02-05-2007 07:40 PM
Three phase in home Bkessler Electrical 10 01-23-2007 08:02 AM
Planer 3 phase???? painterman Electrical 10 12-17-2006 07:33 PM
Another 3 phase problem.... gordfraser Electrical 13 11-10-2006 08:03 PM

Join Now... It's Fast and FREE!

Privacy Badge
I am a professional contractor
I am a DIY Homeowner
ContractorTalk.com is for
PROFESSIONAL CONTRACTORS ONLY!

At ContractorTalk.com we cater exlusivly to professional contractors who make their living as a contractor. Knowing that many homeowners and DIYers are looking for a community to call home, we've created www.DIYChatroom.com DIY Chatroom is full of helpful advices and perfect for DIY homeowners.

Redirecing in 10 seconds
No Thanks
terms of service

Already Have an Account?