What size steel beam to use for load bearing wall???

Hey, i need advice on choosing the correct size steel beam. Please excuse my lack of knownledge (Im a carpenter, not builder), i have the way i want to do this in my head, just not 110% on it because of lack of experience

Ok, I am knocking a wall between a kitchen to a living room. The wall is carrying the the 9x2 Joist overhead, The wall is made of 4 inch block. I want to knock the wall clean through, the opening is 3.5 metres (12 feet approx). I was told to leave a 6 inch bearing on the wall, is this correct.
Would appreciate also if you guys told me how you would approach this job. PS (A friend reckons a 8x4 steel steel beam would be ok.... but i am not so sure)
Thanks alot in advance

brianmvp is offline  
Warning: The topics covered on this site include activities in which there exists the potential for serious injury or death. ContractorTalk.com DOES NOT guarantee the accuracy or completeness of any information contained on this site. Always use proper safety precaution and reference reliable outside sources before attempting any construction or remodeling task!

Join Contractor Talk

Join the #1 Contractor Forum Today - It's Totally Free!

ContractorTalk.com - Are you a Professional Contractor? If so we invite you to join our community and see what it has to offer. Our site is specifically designed for you and it's the leading place for contractors to meet online. No homeowners asking DIY questions. Just fellow tradesmen who enjoy talking about their business, their trade, and anything else that comes up. No matter what your trade is you'll find that ContractorTalk.com is a great community to join. Best of all it's totally free!

Join ContractorTalk.com - Click Here JOIN FOR FREE

Old 07-28-2009, 02:31 PM   #2
Pro
Trade: Framing
 
Join Date: Jan 2009
Location: Utica,NY
Posts: 517
Your friend might be right, but....
Hire an engeneer to look at and size it properly!!
Framer53 is offline  
Old 07-28-2009, 02:40 PM   #3
Pro
 
ChrWright's Avatar
Trade: Builder/Remodeler
 
Join Date: Jul 2007
Location: Indianapolis, Indiana
Posts: 2,058
Blog Entries: 1
Quote:
Originally Posted by brianmvp View Post
Hey, i need advice on choosing the correct size steel beam. Please excuse my lack of knownledge (Im a carpenter, not builder), i have the way i want to do this in my head, just not 110% on it because of lack of experience

Ok, I am knocking a wall between a kitchen to a living room. The wall is carrying the the 9x2 Joist overhead, The wall is made of 4 inch block. I want to knock the wall clean through, the opening is 3.5 metres (12 feet approx). I was told to leave a 6 inch bearing on the wall, is this correct.
Would appreciate also if you guys told me how you would approach this job. PS (A friend reckons a 8x4 steel steel beam would be ok.... but i am not so sure)
Thanks alot in advance

No one can, or should, tell you how to address a structural issue sight unseen... What someone "reckons" can often get you into serious trouble. You've not even given enough info for an educated guess.

A good lumber yard will have someone who can tell you the specs for a given type of beam... lvl... glue lam... etc. But only a structural engineer can tell you exactly what to use for your actual existing conditions.
__________________
Christopher Wright, WrightWorks, LLC
www.WrightWorks.net - Facebook - Christopher Wright, Remodeling Info on Twitter
Indianapolis Remodeling Contractor - Remodeling Photos: Kitchens, Baths, Room Additions, Basements
"Everything has been said before, but since nobody listens we have to keep going back and beginning all over again." --Andre Gide
ChrWright is online now  
Old 07-28-2009, 02:57 PM   #4
Registered User
Trade: Carpentry
 
Join Date: Aug 2008
Posts: 7
Sorry the joist are 9x2 approx 10ft long in each room. so it would be carrying say 22 joist or so.
the floor above carrying 120 sq ft of 12mm softwood flooring,
the same amount of solid oak flooring on top of this.
A 10 ft stud wall made of 3x2 and 9mm plasterboard
2 beds and 1 wardrobe.
If some1 could give me a formula,
I would give it a bash myself, (Its my own house so not to worried about being libel)
brianmvp is offline  
Old 07-28-2009, 03:12 PM   #5
Pro
 
genecarp's Avatar
Trade: LI,NY designer, new homes, renovation work, concre
 
Join Date: Mar 2008
Location: Long Island, NY
Posts: 4,153
http://http://www.contractortalk.com...portant-60787/
__________________
genecarp is online now  
Old 07-28-2009, 03:16 PM   #6
demo master
 
kevjob's Avatar
Trade: Remodeling General Contractor
 
Join Date: Aug 2006
Location: Denver Colorado
Posts: 1,459
Here in Denver when I pull a structural permit and there is no engineers letter they tell you to come back when he signed off on it. No guessing on beams and load points etc...
kevjob is offline  
Old 07-28-2009, 03:19 PM   #7
LRG WoodCrafting
 
Leo G's Avatar
Trade: Professional Sawdust Producer
 
Join Date: May 2005
Location: USA, Connecticut
Posts: 3,886
A big'un
__________________
Measure Twice Cut Once -- It's a lot easier to cut more off then it is to cut MORON.
Quote:
Originally Posted by HusqyPro View Post
Carpenter by day.
Mad scientist by night.
http://lrgwood.com
Leo G is offline  
Old 07-28-2009, 03:23 PM   #8
Pro
 
ChrWright's Avatar
Trade: Builder/Remodeler
 
Join Date: Jul 2007
Location: Indianapolis, Indiana
Posts: 2,058
Blog Entries: 1
Quote:
Originally Posted by brianmvp View Post
Sorry the joist are 9x2 approx 10ft long in each room. so it would be carrying say 22 joist or so.
the floor above carrying 120 sq ft of 12mm softwood flooring,
the same amount of solid oak flooring on top of this.
A 10 ft stud wall made of 3x2 and 9mm plasterboard
2 beds and 1 wardrobe.
If some1 could give me a formula,
I would give it a bash myself, (Its my own house so not to worried about being libel)
You are clearly not a carpenter and don't have the chops for what you're proposing. You need PROFESSIONAL help, ON SITE... and not a "best guess" or "reckoning". You're going to hurt someone with your "bashing"--either your own family, or more likely whomever you sell this spec to...
__________________
Christopher Wright, WrightWorks, LLC
www.WrightWorks.net - Facebook - Christopher Wright, Remodeling Info on Twitter
Indianapolis Remodeling Contractor - Remodeling Photos: Kitchens, Baths, Room Additions, Basements
"Everything has been said before, but since nobody listens we have to keep going back and beginning all over again." --Andre Gide
ChrWright is online now  
Old 07-28-2009, 03:29 PM   #9
Pro
Trade: Home Remodeling
 
Join Date: Dec 2007
Posts: 1,365
Talking

Quote:
Originally Posted by brianmvp View Post
Sorry the joist are 9x2 approx 10ft long in each room. so it would be carrying say 22 joist or so.
the floor above carrying 120 sq ft of 12mm softwood flooring,
the same amount of solid oak flooring on top of this.
A 10 ft stud wall made of 3x2 and 9mm plasterboard
2 beds and 1 wardrobe.
If some1 could give me a formula,
I would give it a bash myself, (Its my own house so not to worried about being libel)

OP=HO??.. Now, let's da fun begins... OOps.. I meant... Da Bloody Monster Bash!!
SelfContract is offline  
Old 07-28-2009, 03:30 PM   #10
demo master
 
kevjob's Avatar
Trade: Remodeling General Contractor
 
Join Date: Aug 2006
Location: Denver Colorado
Posts: 1,459
Quote:
Originally Posted by brianmvp View Post
(Its my own house so not to worried about being libel)
The next guy might care if it falls down or is undersized.
kevjob is offline  
Old 07-28-2009, 03:38 PM   #11
Registered User
Trade: Carpentry
 
Join Date: Aug 2008
Posts: 7
Quote:
Originally Posted by ChrWright View Post
You are clearly not a carpenter and don't have the chops for what you're proposing. You need PROFESSIONAL help, ON SITE... and not a "best guess" or "reckoning". You're going to hurt someone with your "bashing"--either your own family, or more likely whomever you sell this spec to...
Here buddy, I AM a carpenter, I know exactly what im doing, and how im going to do it!
I was just saying, dat I id give the formula a "bash" (attempt) if i got it. I want to make sure the floor above are structurally sound, if i can avoid paying an engineer to do a caluculation dat would only take 2 minutes.
So dont be coming on here patronising me pal, im just looking for some helpful advice
brianmvp is offline  
Old 07-28-2009, 03:46 PM   #12
Pro
 
knucklehead's Avatar
Trade: Framing,Remodeling,General Contractor
 
Join Date: Mar 2009
Location: Kansas City
Posts: 613
I don't think an 8x4 is big enough. I would go with at least an 8x18#
13' long that would be 234 lbs
knucklehead is offline  
Old 07-28-2009, 08:12 PM   #13
Pro
 
knucklehead's Avatar
Trade: Framing,Remodeling,General Contractor
 
Join Date: Mar 2009
Location: Kansas City
Posts: 613
Are you guys ignoring me?
knucklehead is offline  
Old 07-28-2009, 08:23 PM   #14
Al Smith
Trade: Home Improvement contractor since 1983, In building field since 1974, Licensed
 
Join Date: Oct 2007
Location: South River NJ
Posts: 2,145
Send a message via ICQ to A W Smith
there are no magic formulas. there are potential errors of omission.

Quote:
Originally Posted by brianmvp View Post
Sorry the joist are 9x2 approx 10ft long in each room. so it would be carrying say 22 joist or so.
the floor above carrying 120 sq ft of 12mm softwood flooring,
the same amount of solid oak flooring on top of this.
A 10 ft stud wall made of 3x2 and 9mm plasterboard
2 beds and 1 wardrobe.
If some1 could give me a formula,
I would give it a bash myself, (Its my own house so not to worried about being libel)

Brian Brian Brian

If you don't already know the pounds per lineal foot of beam including point loads that you are trying to carry, then you need an engineer. My ex father in law who was a retired staff engineer for the port authority of NY used to size my steel for me. why are you afraid to consult one? they don't bite. It could be a learning experience for you.
__________________
Al Smith
http://www.awsmith.com
A W Smith is offline  
Old 07-28-2009, 08:52 PM   #15
Plausible Deniability
 
JumboJack's Avatar
Trade: General Contractor
 
Join Date: Aug 2007
Location: Lakewood CA.
Posts: 2,224
I would just be safe and go with a three giggawatt beam.Better to be safe than sorry.
__________________
"The problem with socialism is that eventually you run out of other people's money."
JumboJack is offline  
Old 07-29-2009, 04:51 AM   #16
Framer
 
Warren's Avatar
Trade: framing/remodeling
 
Join Date: Feb 2005
Location: NE Ohio
Posts: 996
Quote:
Originally Posted by brianmvp View Post
Here buddy, I AM a carpenter, I know exactly what im doing, and how im going to do it!
I was just saying, dat I id give the formula a "bash" (attempt) if i got it. I want to make sure the floor above are structurally sound, if i can avoid paying an engineer to do a caluculation dat would only take 2 minutes.
So dont be coming on here patronising me pal, im just looking for some helpful advice

Da formula might not be the only thing getting a "bash"

Carpenter here also. Do the math yourself to be sure or call an engineer. Why would you trust the math skills of people on the internet who will hold no liability?
Warren is offline  
Old 07-29-2009, 05:56 AM   #17
Pro
 
joasis's Avatar
Trade: General Contractor
 
Join Date: Mar 2006
Location: Hennessey, Oklahoma
Posts: 4,570
Enough. Closed.
__________________
Ladwig Construction
Hennessey, Oklahoma
405 853 1563

Ladwig Insulation & Construction Services
Serving Oklahoma Statewide
405 314 5802
joasis is offline  
Closed Thread


Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes Rate This Thread
Rate This Thread:

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are Off
Refbacks are Off


Similar Threads
Thread Thread Starter Forum Replies Last Post
Removing studs from a load bearing wall. Russ25nys Framing 36 06-13-2009 08:52 PM
Attaching 2x4 to steel girder Philly Dude Carpentry 20 12-29-2008 11:35 AM
removing a retaining wall Cache Excavation & Site Work 30 07-16-2008 04:57 PM
Steel beam replacement BHI Carpentry 17 02-28-2008 12:03 AM
8" wall size jaymay75 Masonry 5 04-22-2006 12:52 PM